001 First Digit: Loop Speed, Pulse Count and Swinger Setting for zone # 1
The following table lists the options for the loop speed, pulse count and swinger setting. A slow
loop response (150ms) should be entered for motion sensors and contacts. Enter a fast loop
response (50ms) for shock sensors. The three optional pulse count settings can be
programmed at addresses 385-387 and the swinger setting is programmed at address 388. A
full explanation of these features can be found in this section at their respective addresses.
First digit value:
Loop
Speed
Pulse
Count
Swinger
Setting
Value Loop
Speed
Pulse
Count
Swinger
Setting
Value
None - 0 None - 8
Active 1 Active 9
#1 - 2 #1 - A
Slow Active 3 Fast Active B
#2 - 4 #2 - C
Active 5 Active D
#3 - 6 #3 - E
Active 7 Active F
Second Digit: Bypassability, Zone Chime and System ID
The second digit of this address deals with a number of options. Select whether the zone is
bypassable, if the zone chime feature is enabled and to which system the zone is assigned
from the table below.
Second digit value:
Bypassable Chime System Value Bypassable Chime System Value
1 0 1 8
No 2 1 No 2 9
3 2 3 A
No 4 3 Yes 4 B
1 4 1 C
Yes 2 5 Yes 2 D
3 6 3 E
4 7 4 F
002 First Digit: Zone ID for zone#1
Zone ID is the number that can be sent to identify the zone in event code messages to the
central station (event oriented event code table). Generally, the zone ID is the same as the
zone number.
First digit value:
Enter a value between 0 – F for Zone ID
Second Digit: Loop type for zone #1
Select the loop type for this zone from the following list.
Second digit value:
0 – N.C. restore on short, alarm on open.
1 – N.O. alarm on short, restore on open.
2 – EOLR alarm on short, restore on normal, alarm on open.
003 First Digit: Zone type for zone #1
Select a zone type from the following list. For a full explanation of each zone type, see 1.2:
Zones.
First digit value:
0 – Perimeter normal zone. 9 – Verified Fire Zone.
1 – Perimeter primary zone. A – Fire Zone.
2 – Perimeter secondary zone. B – Common Zone.
3 – Perimeter conditional zone. C – Emergency/Holdup (24 Hour).
4 – Interior normal zone. D – Tamper.
5 – Interior primary zone. E – On/Off STAY.
6 – Interior secondary zone. F – On/Off key switch AWAY.
7 – Interior conditional zone.
Note: Zones defined as Emergency/Hold-up, Tamper, Fire and Verified Fire will ignore
the entry/exit delay even if defined.